Product and page has been discontinued. See below list of our current products
Power Quality and Energy Instruments Available from POWERetc
POWERetc offers an extensive line of instruments from the most popular manufacturers including Fluke, Dranetz, Power Standards Lab and PROSyS.
If you are familiar with a particular product and you’re sure it can handle the task you have at hand, then just scroll down this list and select the product you want.
If, on the other hand, you are not sure what you need or want to explore alternatives, then we suggest you go to our selection guide where we will walk you through a series of basic questions to help you arrive at the right tool for your task.
Equipment reliability can be affected by power disturbances. When that question arises it’s important to assess if power quality is “good or bad?” Such investigations can be protracted and expensive. The cellular modem-equipped POWERetc PQube 3 Pass-Thru is a unique and efficient tool for identifying power quality issues and energy use of sensitive electronic equipment - remotely. It gives field service groups the ability to respond to customer concerns swiftly, professionally and very economically. Instead of sending a technician, you just mail the PQube 3 Pass-Thru (PPT) to the troubled site. Thanks to the unit's cellular modem, unit setup, data gathering and report generation are all possible from your desktop computer, laptop or tablet.
Package
Basic Package |
Pricing |
Touchless Troubleshooting with the Cellular Modem-Equipped PQube 3 Pass-Thru
Note: Shipping, Insurance and Taxes are Added to Prices |
Rent & Purchase: |
Trouble-shoot and analyze power quality anywhere and anytime
The PQube 3 Portable is a compact, lightweight, and self-powered unit designed for on the go temporary power analyzing measurement campaigns. It comes in a rugged case with everything you need for a quick and easy set-up. Simply unpack and connect the unit to view the health of the power system, either numerically or graphically, then share the data through screenshots, graphs, or reports. Its ideal for use in harsh environments and enables power professionals to quickly visualize, analyze, and pin-point power and energy disturbances by providing real-time actionable data. Chose the PQube 3 Portable to get fast, reliable, and accurate answers to tough power quality problems.
Features
- 4-quadrant ANSI Class 0.2 revenue–grade energy
- Up to 2 three-phase loads
- Connects direct to voltages up to 690 V
- Class A IEC 61000-4-30 Ed3 certified
- Detects and records high-frequency impulses at 4 MHz
- Measures i and records 2 kHz~150kHz emissions
- Monitors DC power and process parameters with 4 additional AC/DC analog channels
- 32 GB internal flash memory
PQube 3 Rugged
Optimized for remote monitoring of power, energy, and power quality, for indoor or outdoor locations. It is the most economical, and efficient way to monitor power - no special software is needed. The PQube 3 Rugged is equipped with a built-in cellular modem. This time and labor saving feature allows for remote setup to be performed and reports to be sent automatically by email. It is ideal for field service organizations, engineering consultants, contractors, facility owners, and testing organizations to monitor and report on all aspects of power - for individual loads, or an entire plant.
Package
Basic Package |
Pricing |
PQube 3 Rugged Cellular Modem-Equipped including PROSyS PRO-Flex 3000_3 Three Range Probe Set
Note: Shipping, Insurance and Taxes are Added to Prices |
Rent & Purchase: |
PQube 3 Power Analyzer
This compact instrument is simply the best power monitor and real-time sensor you can buy.
It records every type of AC power disturbance – including 4 MHz sampling of impulses – and it is an IEC 61000-4-30, edition 3 Class A certified, ultra-precise revenue-grade energy meter. Monitor up to two three-phase loads, or eight single-phase loads with a single instrument.
It goes beyond AC power too. Records environmental data – such as temperature, humidity and barometric pressure, vibration, 3-axis acceleration – as well as process parameters, including torque, RPM, fuel level, water flow, and more.
Easy to install, easy to use! Delivers ultra-precise results immediately to your inbox.
Electrical Characteristics
Voltage Input | 4 inputs, referenced to earth (Range: 0 ~ 750 VAC (L-N), 0 ~ 1300 VAC (L-L), impedance: 4.8MΩ) |
Current Input | 8 inputs, differential (Range: 0.333Vrms, 10Vpk, 0 ~ 6000 Amp with CTs, impedance: 33.3 kΩ) |
Frequency Range | 50 Hz, 60 Hz, 400 Hz, or 16.67 Hz |
Accuracy | ±0.05% rdg ±0.05% FS typical (10% ~ 150% of nominal) |
Physical Characteristics
Dimensions & weight | 35 mm DIN rail mountable 4.33 in X 2.89 in X 3.08 in (metric: 11.0 cm X 7.34 cm X 7.82 cm) 10.5 oz (300 g) |
Operating Environment | -20 ~ 65 °C (55 °C with PM2 AUX load), 5 ~ 95% RH (inside use), <2000 m above sea level (for EMC immunity, overvoltage, and other conditions, see full specs) |
Temperature and humidity | -20 ~ +80 °C (-4 ~ 176 °F) | 0 ~ 100 % RH |
The Right Tool for Conducting a Connected Load Study to Confirm Panel Capacity
The METSyS Panel Capacity Analyzer (PCA) is a specially-designed instrument for measuring and recording 3- or 4-phase current to confirm the distribution panel's capacity in compliance with NFPA’s National Electrical Code (NEC) 2014 Article 220.87 and meeting the requirements for uniform load calculations in accordance with the requirements of the California Electrical Code (CEC).
The METSyS PCA packaged with POWERetc's proprietary macro-based Excel spreadsheet provides users with the capability of conducting connected load studies of various lengths to meet specific regulatory requirements. This provides a definitive and documented result enabling electrical contractors and facilities engineers to quickly obtain electrical inspection approval when adding new loads to a panel.
The process requires both the calculation of the average current over an extended period in order to confirm that - with planned load additions - will remain less than 80% of the breaker rating(s). In addition, the standard requires that MIN and MAX currents are also determined over the sampling period.
The METSyS logger samples every cycle using an 8-cycle "window" and calculates the average value of the 8-cycles. These readings are accumulated for the user-selected averaging period--10s, 30s, 1m, 5m, 10m, 15m, 30m, 60m--and the average of the averages is saved as the average value for the period and the minimum and maximum sample are saved as the MIN/MAX values. The PCA's MIN/MAX values are really a composite of 8-cycles which will result in understating the peak inrush but is probably more reflective of levels that might cause breaker tripping problems.
The information below details the Basic Portable METSyS 3-Phase Panel Capacity Analyzer package plus a special, permanently-installed Cabinet Current Probe Kit for 480V cabinets.
Package
Basic Package |
Pricing |
METSyS 3-Phase Panel Capacity Analyzer including:
|
Purchase: |
METSyS 3-Phase Panel Capacity Analyzer including:
|
Rental: |
Cabinet Current Probe Kit [CCPK-6] |
Pricing |
POWERetc METSyS Current Probe Kit Facilitates Safe 480V Panel Connected Load Studies.
|
Purchase: |
Electrical Characteristics
Working Voltage | 600V ACrms or DC |
Current Range | 4000 A AC RMS |
Accuracy (45-65hz) | ±1% of reading ±1A. |
Physical Characteristics
Dimensions | 160 (L) x 80 (W) x 45 (D) mm |
Material | ABS |
Operating Temperature | -20 to +65 °C (-4°F to +149°F) |
Downloads
Fluke's flagship power quality and energy monitor; shipped in hard case with voltage cables, and PC Software. With this time and labor saving feature, you can configure the instrument, receive reports and download data to your computer without ever leaving your office!
This is all you need for a host of power quality and energy studies. It can be configured with your choice of clamp-on CT's or flexible current probes. Call us for advice for the best solution for your application.
Ask about two-week rates, local pickup too. We provide up to 2 hours consulting and training included in rental price.
Package
Basic Package |
Pricing |
FLUKE 1777 Three-Phase Power Quality Analyzer Complete with the
|
Rent & Purchase: |
Electrical Characteristics
Voltage Inputs | |
Number of Inputs | 4 inputs, 3 phases and neutral referenced to PE (5 connectors) |
Measurement Category | 1000 V CAT III/600 V CAT IV |
Maximum Input Voltage | 1000 V rms/1000 V DC (1700 Vpk) |
Nominal Voltage Range | Wye and single phase: variable (50 to 1000 V) Delta: variable (100 to 1000 V) IEC 61000-4-30 Class A compliance for the nominal voltages (Vdin) 100 to 690 V |
Input Impedance | 10 MΩ between P-P and P-N, 5 MΩ between P-PE and N-PE |
Bandwidth | DC to 30 kHz for PQ measurements, excluding transients |
Resolution | 24-bit synchronous sampling |
Sampling Frequency | 80 kS/second at 50/60 Hz |
Scaling | 1:1 variable for use of potential transformers |
Voltage Transients | |
Measurement Range | ±8 kV |
Sampling Rate | 1 MS/second 20 MS/second |
Bandwidth | DC to 1 MHz |
Trigger | Adjustable trigger level Triggers on high-frequency components >1.5 kHz |
Resolution | 14-bit synchronous sampling |
Current Inputs | |
Current Inputs | 4 inputs 3 phases and neutral, range selected automatically to attached sensor |
Bandwidth | DC to 30 kHz |
Resolution | 24-bit synchronous sampling |
Sampling Frequency | 80 kS/second at 50/60 Hz |
Scaling | 1:1 variable |
Input Voltage | Clamp: 50 mV/500 mV rms; CF 2.8 Rogowski coil: 15 mV/150 mV rms at 50 Hz, 18 mV/180 mV rms at 60 Hz; CF 4 All at nominal probe range |
Input Impedance | 11 kΩ |
Data Acquisition Voltage and Current | |
Input Mains Frequency | DC, 50/60 Hz ±15% (42.5 to 57.5 Hz, 51 to 69 Hz) |
Topologies | 1-φ, 1-φ IT, split phase, 3-φ delta, 3-φ wye IT, 3-φ aron/blondel (2 element delta), 3-φ delta open leg, 3-φ high leg delta |
Data Storage | 32 GB microSD card (installed) |
Memory Size | Typical 10 logging sessions of 8 weeks with 1-minute intervals and 100 events The number of possible logging sessions and logging period depends on user requirements |
Real-time Accuracy | Internal: 3 ppm (0.26 s per day, 8 s per month) NTP (internet time): depending on internet latency, typical <0.1 s absolute to UTC GPS: <1 ms absolute to UTC |
Read more: Fluke 1777 Three-Phase Power Quality Analyzer with current probes
Equipped with an array of microphones for an expanded field-of-view, the handheld Fluke ii900 Industrial Acoustic Imager (Sonic Industrial Imager) enables maintenance teams to quickly and accurately locate air, gas and vacuum leaks in compressed air systems; even in noisy environments. Specifically designed for noisy production facilities the new SoundSight™ technology is simple to learn and easy to implement. The 7” LCD touchscreen overlays a SoundMap™ on a visual image for quick leak location identification. The straightforward, intuitive interface allows technicians to isolate the sound frequency of the leak to filter out loud background noise. In a matter of hours, the team can inspect the entire plant – during peak operations. For the first time, you can quickly and easily identify the air leak repairs needed to ensure efficient operations and reduce utility bills. Images can be saved and exported for reporting purposes. Never leave air leaks unattended again.
Due to global battery shortages the ii900 Precision Acoustic Imager will be shipped with 1 (one) rechargeable battery Your second battery will follow later. Sorry for any inconvenience this might cause you.
- Do more with the same air compressors – delay the capital expense of purchasing an additional compressor
- Ensure proper air pressure to your pneumatic equipment
- Lower utility costs
- Reduce leak detection time
- Improve reliability in your production line
Designed specifically for load studies, panel capacity, energy and power consumption studies, the Fluke 1730 models are versatile three-phase power loggers. The instrument comes with 3 Fluke 1730-iFlex® 1500 current probes, 150/1500 A range. 3000 Ampere and 6000 Ampere probes are also available. The 1730 model is equipped with wireless Fluke Connect.
Package
Basic Package |
Pricing |
FLUKE 1730 Power Logger System Complete with the
|
Rent & Purchase: |
Electrical Characteristics
Voltage inputs | 4 (3 phases and neutral) max voltage 1000 Vrms, CF 1.7 Impedance 10 MΩ |
Current inputs | 3 (mode selected automatically for the attached sensor) Clamp input: 500 mVrms/50 mVrms; CF 2.8 Rogowski coil input:150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range |
Frequency | Range: 42.5 Hz to 69 Hz Resolution 0.01 Hz Accuracy: ± (0.1 %) |
Voltage | Range: 1000 VAC Resolution: 0.1 V Accuracy: ± (0.2 % + 0.01 %) |
Power factor | Range: 0 <= PF <=1 Resolution: 0.01 Accuracy: ± 0.025 |
Physical Characteristics
Dimensions & Weight | 1730: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in) Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in) 1730: 1.1 kg (2.5 lb) Power supply: 400 g (0.9 lb) |
Operating environment | 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) |
Operating temperature and humidity | -10 °C to +50 °C (14 °F to 122 °F) 10 °C to 30 °C (50 °F to 86 °F) max. 95 % RH 30 °C to 40 °C (86 °F to 104 °F) max. 75 % RH 40 °C to 50 °C (104 °F to 122 °F) max. 45 % RH |
Enclosure protection | IP50 in accordance with EN60529 |
Designed specifically for load studies, panel capacity, energy and power consumption studies, the Fluke 1736/38 models are versatile three-phase power loggers. The instrument comes with 3 Fluke 1730-iFlex® 1500 current probes, 150/1500 A range. 3000 Ampere and 6000 Ampere probes are also available. The 1736/38 model is equipped with wireless Fluke Connect.
Instruments
Instrument | Description | Price |
Fluke 1736 | with 1500A 3.5" probes | Contact for price |
Fluke 1738 | with 1500A 3.5" probes | Contact for price |
Electrical Characteristics
Voltage inputs | Four (3 phases and neutral) Max 1000 Vrms, CF 1.7 Impedance 10 MΩ |
Current inputs | Four (Mode selected automatically for attached sensor) Clamp: 500 mVrms/50 mVrms; CF 2.8 Rogowski coil: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range |
Frequency | Range: 42.5 Hz to 69 Hz Resolution: 0.01 Hz Accuracy: ± (0.1 %) |
Voltage | Range: 1000 V Resolution: 0.1 V Accuracy: ± (0.2 % + 0.01 %) |
Physical Characteristics
Dimensions & Weight | Instrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in) Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in) Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in) Instrument: 1.1 kg (2.5 lb) Power supply: 400 g (0.9 lb) |
Operating environment | 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) |
Operating temperature and humidity | min/max -10 °C to +50 °C (14 °F to 122 °F) 10 °C to 30 °C (50 °F to 86 °F) max. 95 % RH 30 °C to 40 °C (86 °F to 104 °F) max. 75 % RH 40 °C to 50 °C (104 °F to 122 °F) max. 45 % RH |
Enclosure protection | IP50 in accordance with EN60529 |
3-Phase Flexible Current Probe with 3VDC Full-Scale Output available in 24, 36 and 48 inch probe cable lengths.
Electrical Characteristics
Current Ranges | 60A / 600A / 6000A AC RMS (selectable via rotary switch) |
Output Sensitivity | 50mV / 5mV / 0.5mV per A (AC coupled) |
Accuracy (at 25°C) | ± 1% of reading ± 0.1A (60A range) ± 1% of reading ± 1A (600A / 6000A range) |
Physical Characteristics
Probe and Cable Material | Alcryn 2070 NC LATENE 7H2W V0 |
Probe Cable Length | 610mm (24”) / 915mm (36”) / 1220mm (48”) |
Probe Cable Diameter | 9.9mm (nominal) |
Cable Length | 2m (Probe to Integrator box) |
Output | 0.5m long lead terminated with 3 X safety male BNC |